SCADA Data - Monthly Averages
|
Water Treatment Plant |
|||
|
Source |
Parameter |
Units |
Monthly Average |
|
Grand River |
Flow Rate |
ML/d |
36.87 |
|
Brantford POE |
Flow Rate |
ML/d |
30.67 |
|
Grand River |
Turbidity |
NTU |
9.69 |
|
Filter 1 |
Turbidity |
NTU |
0.032 |
|
Filter 2 |
Turbidity |
NTU |
0.032 |
|
Filter 3 |
Turbidity |
NTU |
0.032 |
|
Filter 4 |
Turbidity |
NTU |
0.032 |
|
Filter 5 |
Turbidity |
NTU |
0.033 |
|
Filter 6 |
Turbidity |
NTU |
0.040 |
|
Filter 7 |
Turbidity |
NTU |
0.039 |
|
Filter 8 |
Turbidity |
NTU |
0.034 |
|
Brantford POE |
Turbidity |
NTU |
0.043 |
|
CCC Effluent |
Log Removal |
Not applicable |
9.48 |
|
Brantford POE |
Combined Chlorine |
mg/L |
2.59 |
|
Brantford POE |
Pressure |
psi |
97.05 |
|
Distribution System |
|||
|
Source |
Parameter |
Units |
Monthly Average |
|
Tollgate Reservoir |
Total Chlorine |
mg/L |
2.51 |
|
Park Rd. Reservoir |
Total Chlorine |
mg/L |
2.54 |
|
Northwest Reservoir |
Total Chlorine |
mg/L |
2.52 |
|
Albion St. Booster |
Pressure |
psi |
90.85 |
|
Tollgate Reservoir |
Pressure |
psi |
59.63 |
|
Park Rd. Reservoir |
Pressure |
psi |
79.30 |
|
Northwest Reservoir |
Pressure |
psi |
85.98 |
|
Bell Lane |
Pressure |
psi |
50.74 |
|
Fifth Ave |
Pressure |
psi |
102.76 |
|
Lawren Harris |
Pressure |
psi |
65.10 |
|
St. Andrews |
Pressure |
psi |
93.44 |
|
Empey St. |
Pressure |
psi |
82.68 |
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
|
Source |
Parameter |
Units |
MAC |
AO/OG |
Minimum |
Maximum |
Average |
|
Grand River |
Ammonia |
mg/L |
Not applicable |
Not applicable |
0.00 |
0.23 |
0.10 |
|
Brantford POE |
Ammonia |
mg/L |
Not applicable |
Not applicable |
0.22 |
0.49 |
0.35 |
|
Grand River |
True Colour |
PtCo |
Not applicable |
Not applicable |
11.0 |
28.0 |
17.0 |
|
Brantford POE |
True Colour |
PtCo |
Not applicable |
5 |
0.0 |
2.0 |
0.5 |
|
Brantford POE |
Aluminum |
mg/L |
Not applicable |
0.100 |
0.003 |
0.105 |
0.052 |
|
Grand River |
UV254 |
Not applicable |
Not applicable |
Not applicable |
0.112 |
0.202 |
0.144 |
|
Brantford POE |
UV254 |
Not applicable |
Not applicable |
Not applicable |
0.033 |
0.057 |
0.045 |
|
Brantford POE |
Fluoride |
mg/L |
1.50 |
Not applicable |
0.530 |
0.790 |
0.650 |
|
Brantford POE |
Free chlorine |
mg/L |
Not applicable |
Not applicable |
0.10 |
0.10 |
0.10 |
|
Brantford POE |
Combined Chlorine |
mg/L |
3.00 |
Not applicable |
2.40 |
3.00 |
2.60 |
|
Brantford POE |
Total Chlorine |
mg/L |
Not applicable |
Not applicable |
2.50 |
3.10 |
2.70 |
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.