SCADA Data - Monthly Averages

Water Treatment Plant
Source Parameter Units Monthly Average
Grand River Flow Rate ML/d 37.47
Brantford POE Flow Rate ML/d 32.56
Grand River Turbidity NTU 7.97
Filter 1 Turbidity NTU 0.050
Turbidity NTU 0.031  
Filter 3 Turbidity NTU 0.042
Filter 4 Turbidity NTU 0.042
Filter 5 Turbidity NTU 0.040
Filter 6 Turbidity NTU 0.036
Filter 7 Turbidity NTU 0.045
Filter 8 Turbidity NTU 0.042
Brantford POE Turbidity NTU 0.066
CCC Effluent Log Removal Not applicable 9.76
Brantford POE Combined Chlorine mg/L 2.53
Brantford POE Pressure psi 97.13

SCADA Data - Monthly Averages

Distribution System
Source Parameter Units Monthly Average
Tollgate Reservoir Total Chlorine mg/L 2.51
Park Rd. Reservoir Total Chlorine mg/L 2.55
Northwest Reservoir Total Chlorine mg/L 2.54
Albion St. Booster Pressure psi 90.69
Tollgate Reservoir Pressure psi 58.82
Park Rd. Reservoir Pressure psi 78.60
Northwest Reservoir Pressure psi 84.92
Bell Lane Pressure psi 50.34
Fifth Ave Pressure psi 96.70
Lawren Harris Pressure psi 64.83
St. Andrews Pressure psi 93.30
Empey St. Pressure psi 79.38
Stauffer Rd. Pressure psi 81.32
Hansford Dr Pressure psi 87.53
Pressure psi 53.82  

Definitions:

SCADA - Supervisory Control and Data Acquisition

O.O.S - Out of Service

CCC - Chlorine Contact Chambers

Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.

Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

Treatment Operators Analysis

Treatment Operators Analysis
Source Parameter Units MAC AO/OG Minimum Maximum Average
Grand River Ammonia mg/L Not applicable Not applicable 0.08 0.25 0.16
Brantford POE Ammonia mg/L Not applicable Not applicable 0.19 0.42 0.30
Grand River True Colour PtCo Not applicable Not applicable 13 29 20
Brantford POE True Colour PtCo Not applicable 5 0 2 1
Brantford POE Aluminum mg/L Not applicable 0.100 0.010 0.069 0.026
Grand River UV254 Not applicable Not applicable Not applicable 0.125 0.194 0.163
Brantford POE UV254 Not applicable Not applicable Not applicable 0.027 0.073 0.051
Brantford POE Fluoride mg/L 1.50 Not applicable 0.54 0.72 0.64
Brantford POE Free chlorine mg/L Not applicable Not applicable 0.10 0.10 0.10
Brantford POE Combined Chlorine mg/L 3.00 2.20 2.70
Brantford POE Total Chlorine mg/L Not applicable Not applicable 2.30 2.80 2.64

Definitions:

MAC - Maximum Acceptable Concentration

AO/OG - Aesthetic Objective/Operational Guideline

Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

SCADA Data - Monthly Averages 

Water Treatment Plant

Source

Parameter

Units

Monthly Average

Grand River

Flow Rate

ML/d

36.75

Brantford POE

Flow Rate

ML/d

33.08

Grand River

Turbidity

NTU

3.74

Filter 1

Turbidity

NTU

0.061

Filter 2

Turbidity

NTU

0.031

Filter 3

Turbidity

NTU

0.038

Filter 4

Turbidity

NTU

0.039

Filter 5

Turbidity

NTU

0.060

Filter 6

Turbidity

NTU

0.038

Filter 7

Turbidity

NTU

0.045

Filter 8

Turbidity

NTU

0.040

Brantford POE

Turbidity

NTU

0.039

 

CCC Effluent

Log Removal

Not applicable

9.63

Brantford POE

Combined Chlorine

mg/L

2.52

 

Brantford POE

Pressure

psi

97.34

 

SCADA Data - Monthly Averages

Distribution System

Source

Parameter

Units

Monthly Average

Tollgate Reservoir

Total Chlorine

mg/L

2.49

Park Rd. Reservoir

Total Chlorine

mg/L

2.46

Northwest Reservoir

Total Chlorine

mg/L

2.54

Albion St. Booster

Pressure

psi

90.73

Tollgate Reservoir

Pressure

psi

58.77

Park Rd. Reservoir

Pressure

psi

78.67

Northwest Reservoir

Pressure

psi

84.14

Bell Lane

Pressure

psi

50.51

Fifth Ave

Pressure

psi

97.04

Lawren Harris

Pressure

psi

64.99

St. Andrews

Pressure

psi

93.37

Empey St.

Pressure

psi

82.69

Stauffer Rd.

Pressure

psi

81.27

Hansford Dr

Pressure

psi

87.58

Definitions:

SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

Treatment Operators Analysis

Treatment Operators Analysis

Source

Parameter

Units

MAC

AO/OG

Minimum

Maximum

Average

Grand River

Ammonia

mg/L

Not applicable

Not applicable

0.05

0.27

0.17

Brantford POE

Ammonia

mg/L

Not applicable

Not applicable

0.20

 

0.45

0.31

Grand River

True Colour

PtCo

Not applicable

Not applicable

11

21

15.75

Brantford POE

True Colour

PtCo

Not applicable

5

0

2

0.68

Brantford POE

Aluminum

mg/L

Not applicable

0.100

0.015

0.044

0.030

Grand River

UV254

Not applicable

Not applicable

Not applicable

0.121

0.146

0.133

Brantford POE

UV254

Not applicable

Not applicable

Not applicable

0.035

0.071

0.053

Brantford POE

Fluoride

mg/L

1.50

Not applicable

0.51

0.78

0.69

Brantford POE

Free chlorine

mg/L

Not applicable

Not applicable

0.10

0.10

0.10

Brantford POE

Combined Chlorine

mg/L

3.00

Not applicable

2.40

2.70

2.52

Brantford POE

Total Chlorine

mg/L

Not applicable

Not applicable

2.50

2.80

2.62

Definitions:

MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

SCADA Data - Monthly Averages
Water Treatment Plant

SCADA Data - Monthly Averages - Water Treatment Plant
Source Parameter Units Monthly Average
Grand River Flow Rate ML/d 34.34
Brantford POE Flow Rate ML/d 30.33
Grand River Turbidity NTU 15.24
Filter 1 Turbidity NTU 0.064
Filter 2 Turbidity NTU 0.036
Filter 3 Turbidity NTU 0.041
Filter 4 Turbidity NTU 0.043
Filter 5 Turbidity NTU 0.065
Filter 6 Turbidity NTU 0.042
Filter 7 Turbidity NTU 0.048
Filter 8 Turbidity NTU 0.045
Brantford POE Turbidity NTU 0.038
CCC Effluent Log Removal

Not applicable

9.73
Brantford POE Combined Chlorine mg/L 2.53
Brantford POE Pressure psi 97.20

SCADA Data - Monthly Averages
Distribution System

SCADA Data - Monthly Averages
Source Parameter Units Monthly Average
Tollgate Reservoir Total Chlorine mg/L 2.43
Park Rd. Reservoir Total Chlorine mg/L 2.47
Northwest Reservoir Total Chlorine mg/L 2.50
Albion St. Booster Pressure psi 90.83
Tollgate Reservoir Pressure psi 58.69
Park Rd. Reservoir Pressure psi 78.79
Northwest Reservoir Pressure psi 84.76
Bell Lane Pressure psi 50.58
Fifth Ave Pressure psi 98.82
Lawren Harris Pressure psi 66.21
St. Andrews Pressure psi 93.85
Empey St. Pressure psi 83.62
Stauffer Rd. Pressure psi 81.74
Hansford Dr Pressure psi 87.64
Colborne St Pressure psi 53.93

Definitions:

SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

Treatment Operators Analysis

Treatment Operators Analysis
Source Parameter Units MAC AO/OG Minimum Maximum Average
Grand River Ammonia mg/L Not applicable Not applicable 0.05 0.29 0.14
Brantford POE Ammonia mg/L Not applicable Not applicable 0.19 0.43 0.32
Grand River True Colour PtCo Not applicable Not applicable 13 47 23
Brantford POE True Colour PtCo Not applicable 5 0 3 1
Brantford POE Aluminum mg/L Not applicable 0.100 0.006 0.034 0.031
Grand River UV254 Not applicable Not applicable Not applicable 0.122 0.202 0.160
Brantford POE UV254 Not applicable Not applicable Not applicable 0.029 0.069 0.049
Brantford POE Fluoride mg/L 1.50 Not applicable 0.62 0.79 0.70
Brantford POE >

Free Chlorine

mg/L Not applicable Not applicable 0.10 0.10 0.10
Brantford POE Combined Chlorine mg/L 3.00 Not applicable 2.30 2.80 2.55
Brantford POE Total Chlorine mg/L Not applicable Not applicable 2.40 2.90 2.65

Definitions:

MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

SCADA Data - Monthly Averages

Water Treatment Plant

Water Treatment Plant
Source Parameter Units Monthly Average
Grand River Flow Rate ML/d 34.26
Brantford POE Flow Rate ML/d 30.79
Grand River Turbidity NTU 25.16
Filter 1 Turbidity NTU 0.070
Filter 2 Turbidity NTU 0.040
Filter 3 Turbidity NTU 0.050
Filter 4 Turbidity NTU 0.050
Filter 5 Turbidity NTU 0.070
Filter 6 Turbidity NTU 0.050
Filter 7 Turbidity NTU 0.060
Filter 8 Turbidity NTU 0.050
Brantford POE Turbidity NTU 0.050
CCC Effluent Log Removal Not applicable 11.82
Brantford POE Combined Chlorine mg/L 2.55
Brantford POE Pressure psi 97.02

SCADA Data - Monthly Averages

Distribution System

Distribution System
Source Parameter Units Monthly Average
Tollgate Reservoir Total Chlorine mg/L 2.31
Park Rd. Reservoir Total Chlorine mg/L 2.32
Northwest Reservoir Total Chlorine mg/L 2.22
Albion St. Booster Pressure psi 90.70
Tollgate Reservoir Pressure psi 58.85
Park Rd. Reservoir Pressure psi 78.66
Northwest Reservoir Pressure psi 83.76
Bell Lane Pressure psi 50.37
Fifth Ave Pressure psi 98.82
Lawren Harris Pressure psi 66.21
St. Andrews Pressure psi 93.85
Empey St. Pressure psi 79.63
Stauffer Rd. Pressure psi 82.04
Hansford Dr Pressure psi 87.50
Colborne St Pressure psi 52.85

Definitions:

SCADA - Supervisory Control and Data Acquisition

O.O.S - Out of Service

CCC - Chlorine Contact Chambers

Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.

Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

Treatment Operators Analysis

Treatment Operators Analysis
Source Parameter Units MAC AO/OG Minimum Maximum Average
Grand River Ammonia mg/L Not applicable Not applicable 0.04 0.26 0.14
Brantford POE Ammonia mg/L Not applicable Not applicable 0.02 0.53 0.36
Grand River True Colour PtCo Not applicable Not applicable 20 38 27
Brantford POE True Colour PtCo Not applicable 5 0 2 1
Brantford POE Aluminum mg/L Not applicable 0.100 0.013 0.082 0.044
Grand River UV254 Not applicable Not applicable Not applicable 0.156 0.224 0.194
Brantford POE UV254 Not applicable Not applicable Not applicable 0.04 0.065 0.051
Brantford POE Fluoride mg/L 1.50 Not applicable 0.60 0.79 0.70
Brantford POE Free chlorine mg/L Not applicable Not applicable 0.10 0.10 0.10
Brantford POE Combined Chlorine mg/L 3.00 Not applicable 1.50 2.80 2.57
Brantford POE Total Chlorine mg/L Not applicable Not applicable 1.60 2.90 2.67

Definitions:

MAC - Maximum Acceptable Concentration

AO/OG - Aesthetic Objective/Operational Guideline

Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

SCADA Data - Monthly Averages - Water Treatment Plant
Source Parameter Units Monthly Average
Grand River Flow Rate ML/d 37.06
Brantford POE Flow Rate ML/d 33.53
Grand River Turbidity NTU 6.73
Filter 1 Turbidity NTU 0.06
Filter 2 Turbidity NTU 0.05
Filter 3 Turbidity NTU 0.05
Filter 4 Turbidity NTU 0.05
Filter 5 Turbidity NTU 0.05
Filter 6 Turbidity NTU 0.05
Filter 7 Turbidity NTU 0.06
Filter 8 Turbidity NTU 0.06
Brantford POE Turbidity NTU 0.05
CCC Effluent Log Removal Not applicable 14.15
Brantford POE Combined Chlorine mg/L 2.59
Brantford POE Pressure psi 97.27
SCADA Data - Monthly Averages - Distribution System
Source Parameter Units Monthly Average
Tollgate Reservoir Total Chlorine mg/L 2.23
Park Rd. Reservoir Total Chlorine mg/L 2.24
Northwest Reservoir Total Chlorine mg/L 2.30
Albion St. Booster Pressure psi 90.26
Tollgate Reservoir Pressure psi 58.96
Park Rd. Reservoir Pressure psi 78.36
Northwest Reservoir Pressure psi 83.43
Bell Lane Pressure psi 50.49
Fifth Ave Pressure psi 98.82
Lawren Harris Pressure psi 66.21
St. Andrews Pressure psi 93.85
Empey St. Pressure psi 81.75
Stauffer Rd. Pressure psi 81.29
Hansford Dr Pressure psi 86.31
Colborne St Pressure psi 53.97

Definitions:

SCADA - Supervisory Control and Data Acquisition

O.O.S - Out of Service

CCC - Chlorine Contact Chambers

Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.

Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

Treatment Operators Analysis
Source Parameter Units MAC AO/OG Minimum Maximum Average
Grand River Ammonia mg/L Not applicable Not applicable 0.02 0.13 0.08
Brantford POE Ammonia mg/L Not applicable Not applicable 0.28 0.52 0.39
Grand River True Colour PtCo Not applicable Not applicable 12 26 19
Brantford POE True Colour PtCo Not applicable 5 0 2 1
Brantford POE Aluminum mg/L Not applicable 0.100 0.03 0.25 0.13
Grand River UV254 Not applicable Not applicable Not applicable 0.139 0.580 0.168
Brantford POE UV254 Not applicable Not applicable Not applicable 0.030 0.082 0.050
Brantford POE Fluoride mg/L 1.50 Not applicable 0.55 0.77 0.66
Brantford POE Free chlorine mg/L Not applicable Not applicable 0.10 0.10 0.10
Brantford POE Combined Chlorine mg/L 3.00 Not applicable 2.40 2.80 2.60
Brantford POE Total Chlorine mg/L Not applicable Not applicable 2.50 2.90 2.70

Definitions:

MAC - Maximum Acceptable Concentration

AO/OG - Aesthetic Objective/Operational Guideline

Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.

Summary will be shared once information becomes available

Summary will be shared once information becomes available

Summary will be shared once information becomes available

Summary will be shared once information becomes available

Summary will be shared once information becomes available

Summary will be shared once information becomes available

Summary will be shared once information becomes available

Contact Us

City of Brantford
58 Dalhousie Street
P.O. Box 818
Brantford, Ontario
N3T 2J2 

519-759-4150

Subscribe to receive updates from the City

Stay up-to-date on the city’s activities, events, programs and operations by subscribing to our newsroom.